IPT2300 PSC Loop Impedance Tester with Anti-RCD Trip Feature
20/200/2000Ω loop impedance test ranges
PSC measurement to 20kA
Anti trip technology allows 15mA low current loop testing without bypassing all RCD types
25A high current test for fast tests in noisy environments and where tripping RCDs is not a consideration.
Fully protected against phase to phase connection
Earth probe for testing exposed metalwork
Colour coded LEDs for instant check of correct wiring status
Complies with BS 7671 wiring regulations
Complies with safety standard EN610101-1 CAT III 300V
Range
Test Current
Accuracy
Loop
Normal
0 → 20Ω
25A for 10ms
3% rdg ±4 digits
Loop
Normal
0 → 200Ω
2.3A for 40ms
3% rdg ±4 digits
Loop
Normal
0 → 2000Ω
15mA for 360ms
3% rdg ±4 digits
Loop
Anti-Trip
0 → 20Ω
P-N 25A
N-E 15mA or less. *resistance
P-N must be = 20Ω
3% rdg ±6 digits
Loop
Anti-Trip
0 → 200Ω
P-N 25A
N-E 15mA or less. *resistance
P-N must be = 20Ω
3% rdg ±6 digits
PSC
Normal
0 → 20kA
25A
Determined by loop accuracy
PSC
Normal
0 → 2000A
2.5A
Determined by loop accuracy
PSC
Normal
0 → 200A
2.3A
Determined by loop accuracy
PSC
Anti-Trip
0 → 20kA
P-N 25A
N-E 15mA or less. *resistance
P-N must be = 20Ω
Determined by loop accuracy
PSC
Anti-Trip
0 → 2000A
P-N 25A
N-E 15mA or less. *resistance
P-N must be = 20Ω
Determined by loop accuracy
PSC
Anti-Trip
0 → 200A
P-N 25A
N-E 15mA or less. *resistance
P-N must be = 20Ω
Determined by loop accuracy
Voltage Measurement
100 → 300V 50Hz
-
2% ±4 digits
Supplied with
BS1363 mains socket test lead, distribution board fused test leads with earth lead crocodile clip, instruction manual test lead pouch and 8 x AA alkaline batteries.
ISO-TECH Loop Testers