PAX Industrial Indicator, Current, Voltage, Temperature, Resistance
Can be used as a highly flexible and precise laboratory instrument
The sturdy plastic housing is also designed for tough industrial use
Can be quickly and securely projected via PC or directly using 5 buttons
Can be retrofitted with plug-in options
PAX D for standard / analogue signals
PAX T for thermocouples and PT100
Inputs:
PAX D: Standard / analogue signals: ±200 mV, ±2 V, ±20 V, ±300 V, ±200 μA, ±2 mA, ±20 mA, ±200 mA, ±2 A and 100 Ω, 1000 Ω, 10 kΩ
PAX T: Thermocouples: types T, E, J, K, R, S, B, N, C.
Resistance thermometer: PT100
Display capacity:
5-digit, 14 mm high red LED. Device freely definable. Digital display freely scalable. Linearisation with 16 dots for PAX D.
Indicators: MAX, MIN, TOT (total) SP1 → SP4 (output status)
Backlit device:
Physical device very easily attached behind the display.
Procedure:
Programmed using front buttons, or using Windows software on the PC. During programming, it is decided which displays and inputs are possible after activation of the programming lockout and which remain locked.
User inputs:
3 programmable inputs available. Functions: reset total / display / min. value / max. value, Tara, pressure build-up, programming lockout etc. Adjustable by switching using jumper PNP or NPN.
Total counter:
10-digit total counter can create a product from the signal and the time. Either totalled automatically or with user input. Time base and factor make the device flexible.
Voltage supply:
230 VAC: 85 → 250 VAC 50 / 60 Hz or 24 VDC: 11 → 36 VDC / 24 VAC
Sensor power supply:
PAX D: 24 VDC ±5%, regulated, max. 50 mA, reference voltage and current.
Measuring rate:
20 measurements/s, A/D transducer 16-bit resolution
Output option cards:
User can easily retrofit various output cards. At the most, every device can hold an interface card, a relay output card and an analogue output card.
Plug-in
Interface card:
1. RS 232, Half-duplex
...